2 822x/ 824x, 3 8218-v003, 2 display of the controller status – Lenze 8200 Frequency inverters User Manual
Page 135: 822x/824x, 8218-v003, Display of the controller status, During operation

During operation
8200SHB0199
6-2
6.1.2
822X/824X
-
The controllers 822X/824X have a temperature-dependent fan circuit:
- The fans are only activated when the heat sink temperature, which is a
fixed factory setting, is exceeded.
6.1.3
8218-V003
-
For use of the variant 8218-V003 with the Lenze convection cooling system:
- Depending on the application conditions, the temperature monitoring
(message ”OH”) can be activated during low-noise operation with a
16 kHz chopper frequency (C018=-5-).
6.2
Display of the controller status
During operation without an operating module, the operating state of the controller
is displayed on two LEDs at the front of the unit.
LED
Operating status
green
red
on
off
Controller enabled
on
on
Mains switched on and automatic start inhibited (AS_LC)
blinking
off
Controller inhibited
off
blinking every second
Fault message
off
blinking every 0.4 seconds
Undervoltage switch-off
off
off
Programming mode (only 820X)