3 normalisation of an application datum, Normalisation of an application datum, Configuration – Lenze 8200 Frequency inverters User Manual
Page 200
Configuration
8200SHB0199
7-63
7.6.3
Normalisation of an application datum
820X setting range: This function is not available.
Setting range 821X/822X/824X:
Code
Name
Possible settings
IMPORTANT
Code
Name
Lenze
Choice
Info
IMPORTANT
C500* Display factor
Application datum
numerator
821X/822X/824X
2000
1
{1}
25000
C501* Display factor for
process variable
denominator
821X/822X/824X
10
1
{1}
25000
Function
-
Adaptation of field-frequency related parameters
C010, C011, C017, C019, C037, C038, C039, C050, or
C010, C011, C017, C019, C037, C038, C039, C046, C049, C050, C051, C181, C625, C626,
C627 (series “HVAC”)
to an application datum to be controlled, e.g. pressure, temperature, flow rate, humidity or speed.
-
The normalisation implements an absolute or relative selection of an application datum.
-
All codes indicated are normalised at the same time.
Adjustment
The display value is calculated from:
CXXX
C011
200 ô
C500
C501
Example
The speed setpoint is to be input and displayed as relative or absolute value.
Values: P
set
= 5 bar, if f
dmax
= 50 Hz (C011)
a) Relative normalisation in %
100.00 (%)
50
200 ô
4000
10
e.g. C500 = 4000, C501 = 10
b) Absolute normalisation in physical units
5.00 (bar)
50
200 ô
200
10
e.g. C500 = 200; C501 = 10
Important
-
All codes indicated above are normalised at the same time.
-
After a normalisation, the output frequency [Hz] (C050) can only be recalculated with the display
factors C500 and C501.