3 adapt machine data, 1 determine speed range (fdmin, fdmax), Adapt machine data – Lenze 8200 Frequency inverters User Manual
Page 108: Determine speed range (fdmin, fdmax), Commissioning, 1 determine speed range (f
Commissioning
8200SHB0199
5-3
5.3
Adapt machine data
5.3.1
Determine speed range (f
dmin,
f
dmax)
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C010 Minimum field
frequency
820X
0.00
0.00
{0.05 Hz}
480.00
821X/822X/
824X
0.00
0.00
{0.02 Hz}
480.00
C011 Maximum field
frequency
820X
50.00
30.00
{0.05 Hz}
480.00
821X/822X/
824X
50.00
7.50
{0.02 Hz}
480.00
Function
The speed range required for the application can be selected via the input of field frequencies f
dmin
and f
dmax
:
-
f
dmin
corresponds to the speed at 0 % speed setpoint selection.
-
f
dmax
corresponds to the speed at 100 % speed setpoint selection.
Adjustment
Relation between field frequency and synchronous motor speed:
n
Nsyn
f
dmax
ô 60
p
n
Nsyn
Synchronous motor speed [min
-1
]
f
dmax
Max. field frequency [Hz]
p
No. of pole pairs (1, 2, 3, ...)
Example: 4 pole asynchronous motor:
p = 2, f
dmax
= 50 Hz
n
Nsyn
50
ô 60
2
1500 min
Å1
Important
-
With the setting of f
dmin
> f
dmax
, the field frequency is limited to f
dmax
.
-
With setpoint selection via JOG values, f
dmax
acts as limitation.
-
f
dmax
is an internal normalisation variable:
- Use the LECOM interface only for important modifications, when the controller is inhibited.
-
Observe the maximum speed of the motor!
-
f
dmin
is only effective:
- With analog setpoint input.
- With the motor potentiometer function ”DOWN”.
Special features
fd
C011
(fdmax)
C010
(fdmin)
0 %
100 %