5 skip frequencies, Skip frequencies, Configuration – Lenze 8200 Frequency inverters User Manual
Page 170: Only “hvac” controllers

Configuration
8200SHB0199
7-33
7.5.9.5
Skip frequencies
Only “HVAC” controllers
Code
Name
Possible settings
IMPORTANT
Lenze
Choice
Info
C625* Skip frequency 1
480.00 0.00
{0.02 Hz}
480.00
C626* Skip frequency 2
480.00 0.00
{0.02 Hz}
480.00
C627* Skip frequency 3
480.00 0.00
{0.02 Hz}
480.00
C628 Bandwidth of skip
frequencies
0.00
0.00
{0.01 %}
100.00
Function
With certain output frequencies, mechanical resonances might occur in the drive (e.g. fan). The skip
frequencies eliminate these unwanted output frequencies. The bandwidth (
af) determines the
range of skip frequencies.
With skip frequency = 480.00 Hz, the function is not active.
The function is within the frequency setpoint range of the ramp function generator.
Adjustment
-
Set the required skip frequencies under C625, C626, C627.
-
C628 defines the bandwidth of skip frequencies.
- Calculate the bandwidth (
Df) for the corresponding skip frequency:
of [Hz] Skip frequency [Hz] ô
C628 [%]
100 %
Important
-
The skip frequencies are only effective in the main setpoint channel (see signal flow chart).
-
C625, C626, C627, C628 are only stored in parameter set 1.
f
skip1
f
skip3
f
skip2
C625
C626
C627
C628
C628
C628
fd
set1
fd
set2
f
f
f
FIG 7-3
Skip frequencies and their bandwidth (
a
f)