Configuration – Lenze 8200 Frequency inverters User Manual
Page 218
Configuration
8200SHB0199
7-81
Code
IMPORTANT
Possible settings
Name
Code
IMPORTANT
Info
Choice
Lenze
Name
C117
¤ Function relay K2
822X/824X
-0-
-0-
Ready for operation
-1-
TRIP fault message
-2-
Motor is running
-3-
Motor is running / CW rotation
-4-
Motor is running / CCW rotation
-5-
Field frequency f
d
= 0
-6-
f
dset
reached
-7-
Q
min
reached
-8-
I
max
reached
-9-
Overtemperature (
J
max
-10
C)
-10-
TRIP or Q
min
or IMP
-11-
PTC warning
Page 7-65 ff
C119
¤ Function PTC
822X/824X
-0-
-0-
PTC input not active
-1-
PTC input active, TRIP and pulse
inhibit will be set
-2-
PTC input active
Warning
Page 7-72
C120 I
2
kt switch-off
Page 7-71
C120
822X/824X
0
0
{1 %}
100
If C120 = 0, the
function is not active
C125
¤* LECOM baud rate
-0-
-0-
9600 baud
-1-
4800 baud
-2-
2400 baud
-3-
1200 baud
-4-
19200 baud
Only for LECOM
applications
C142
¤ Start condition
-1-
-0-
Automatic start inhibited,
flying-restart circuit not active
-1-
Automatic start, if term. 28 HIGH,
flying-restart circuit not active
-2-
Automatic start inhibited,
flying-restart circuit active
-3-
Automatic start, if term. 28 HIGH,
flying-restart circuit active
Page 7-49
C144
¤ Chopper-frequency
reduction
Page 7-29
821X/822X/824X
-1-
-0-
No chopper-frequency lowering
-1-
Automatic chopper frequency
reduction at
J
max
- 10
C
C161* Current fault
Page 8-2
C162* Last fault
Page 8-2
Display only
C163* Last but one fault
Page 8-2
Display only
C164* Last but two fault
Page 8-2
C170
¤ TRIP-reset selection
-0-
TRIP reset by pressing the STP key
or LOW signal at ctrl. enable or
fieldbus
-1-
Auto TRIP reset or TRIP reset by
pressing the STP key or LOW signal
at ctrl. enable or fieldbus
Page 8-4
C171 Deceleration for
Auto-TRIP reset
0.00
0.00
{0.01 s}
60.00 Page 8-4
C178* Operating time
Page 7-64
Display only
Show/Hide Bookmarks