4 types 824x, Types 824x, Technical data – Lenze 8200 Frequency inverters User Manual
Page 52
Technical Data
8200SHB0199
3-20
3.5.4
Types 824X
120 % overload
Type
8241
8242
8243
8244
8245
8246
Mains current
with mains filter/mains choke
I
mains
[A]
1.7
2.8
5.0
8.8
15.0
20.5
Data for mains operation with 3 AC / 400 V / 50 Hz/60 Hz ; 460 V
$ V
DC
$ 620 V
Motor power (4 pole ASM)
at 4 kHz/8 kHz
*
P
r
[kW]
0.55
1.1
2.2
4.0
7.5
11.0
Motor power (4 pole ASM)
at 4 kHz/8 kHz
*
P
r
[hp]
0.75
1.5
2.9
5.4
10.0
15.0
Output power U, V, W
at 4 kHz/8 kHz
*
S
r4
[kVA]
S
r8
[kVA]
1.3
1.0
2.1
1.7
3.8
2.7
6.5
4.8
11.1
9.0
16.3
16.3
Output
current
4 kHz
*
I
r4
[A]
1.8
3.1
5.5
9.2
16.0
23.5
Output
current
8 kHz
*
I
r8
[A]
1.5
2.5
3.9
7.0
13.0
23.5
12 kHz
*
I
r12
[A]
1.35
2.2
3.5
6.3
11.7
20.0
16 kHz
*
I
r16
[A]
1.2
2.0
3.1
5.6
10.4
16.5
Noise optimised 4 kHz
*2)
I
r4
[A]
1.5
2.5
3.9
7.0
13.0
23.5
Noise optimised 8 kHz
*2)
I
r8
[A]
1.3
2.2
2.9
6.0
11.1
20.0
Noise optimised 12 kHz
*
I
r12
[A]
1.3
2.1
3.4
6.1
11.3
19.4
Noise optimised 16 kHz
*
I
r16
[A]
1.1
1.8
2.9
5.2
9.7
15.2
Max.
output
I
rmax4
[A]
2.25
3.6
6.6
11.0
19.5
35.3
Max.
output
current
8 kHz
*
I
r8
[A]
2.2
3.7
5.8
10.5
19.5
35
current
for
12 kHz
*
I
r12
[A]
2.0
3.3
5.2
9.5
17.5
30.0
for
60 s
1)
16 kHz
*
I
r16
[A]
1.8
3.0
4.7
8.4
15.6
24.6
60 s
1)
Noise optimised 4 kHz
*2)
I
r4
[A]
2.3
3.8
5.8
10.5
19.5
35.5
Noise optimised 8 kHz
*2)
I
r8
[A]
2.0
3.2
5.0
7.8
14.5
22.9
Noise optimised 12 kHz
*
I
r12
[A]
1.9
3.2
5.1
9.1
16.5
29.0
Noise optimised 16 kHz
*
I
r16
[A]
1.6
2.7
4.3
7.8
14.5
22.9
Power loss (operation with I
rx
)
P
loss
[W]
50
65
115
165
260
360
1)
The currents apply to a periodical load cycle with 1 minute overcurrent with the current mentioned here and
2 minutes base load with 75 % I
rx
.
2)
Only with variant “HVAC”
*
Chopper frequency of the inverter
For more data see chapter 3.4.6 and chapter 3.4.7.
Show/Hide Bookmarks