4 normalisation of an application datum, Normalisation of an application datum, Commissioning – Lenze 8200 Frequency inverters User Manual
Page 120

Commissioning
8200SHB0199
5-15
5.4.2.4
Normalisation of an application datum
820X setting range:
Function not available.
Setting range 821X/822X/824X:
Code
Name
Possible settings
IMPORTANT
Code
Name
Lenze
Choice
Info
IMPORTANT
C500* Display factor
Application datum -
numerator
2000
1
{1}
25000
C501* Display factor
Application datum -
denominator
10
1
{1}
25000
Function
Adaptation of field-frequency related parameters
-
C010, C011, C017, C019, C037, C038, C039, C046, C049, C050 and
-
for controllers of the “HVAC” series C051, C181, C625, C626, C627 additionally
to an application datum to be controlled, e.g. pressure, temperature, flow rate, humidity or speed.
The normalisation
-
implements an absolute or relative selection or display of an application datum,
-
is always carried out simultaneously for all codes indicated.
Adjustment
The display value is calculated from:
CXXX
C011
200 ô
C500
C501
Example
The speed setpoint is to be input and displayed as relative or absolute value.
Values: P
set
= 5 bar, if f
dmax
= 50 Hz (C011)
a) Relative normalisation in %
100.00 (%)
50
200 ô
4000
10
e.g. C500 = 4000, C501 = 10
b) Absolute normalisation in physical units
5.00 (bar)
50
200 ô
200
10
e.g. C500 = 200; C501 = 10
Important
-
All codes indicated above are normalised at the same time.
-
After a normalisation, the output frequency [Hz] (C050) can only be recalculated with the display
factors C500 and C501.
Show/Hide Bookmarks