Troubleshooting and fault elimination
8200SHB0199
8-1
8
Troubleshooting and fault elimination
Occuring faults can be easily recognized through the display elements or status
information (chapter 8.1).
The faults can be analysed with the history buffer (chapter 8.2) and the list in
chapter 8.3, which helps you to eliminate the faults.
8.1
Troubleshooting
8.1.1
Display at the controller
During operation without operating module, two LEDs at the front indicate the
operating status of the controller.
LED
Operating status
green
red
Operating status
on
off
Controller enabled
on
on
Mains switched on, automatic start inhibited (AS_LC)
blinking off
Controller inhibited
off
blinking every second
Fault message, check under C161
off
blinking every 0.4 seconds
Undervoltage switch-off
off
off
Programming mode (only 820X)
8.1.2
Display at the operating module
Status message in the display indicate the controller status.
Display
Meaning
OV
Overvoltage
UV
Undervoltage
IMAX
Set current limit exceeded
TEMP
Heat sink temperature near switch-off limit