Configuration – Lenze 8200 Frequency inverters User Manual
Page 172

Configuration
8200SHB0199
7-35
Normalisation
-
Adaptation of a field related parameter to an application datum to be controlled (e.g. pressure,
temperature, flow rate, humidity, speed) under C500 and C501.
-
The following codes are normalised at the same time:
- C010, C011 C017, C019, C037, C038, C039, C046, C049, C050, C051, C181, C625, C626,
C627
-
After a normalisation, the output frequency [Hz] (C050) can only be recalculated with the display
factors C500 and C501 (see formulas in chapter 7.6.3).
-
In factory setting, all field related parameters refer to the frequency. Input and display in Hz. The
values of C037, C038, C039, C046, C051, C181 refer to C011.
Factory setting
A percentage of the input or display values
corresponds to the frequency in Hz.
0 %
100 % Setpoint or act. value
C011
[Hz]
Adjustment
The value set under C071 correspond to the following integral action times T
n
.
Values under C071
Integral action time T
n
10 ... 5000
10 ms ... 5000 ms
5000 ... 6000
5 s ... 10 s
6000 ... 7000
10 s ... 100 s
7000 ... 8000
100 s ... 1000 s
8000 ... 9999
1000 s ... 9999 s
Guide values for pressure
control and flow rate
The values in the following table are for guidance for pressure and flow-rate controls. A fine
adjustment is therefore always necessary.
C070, C071 and C072 must be set so that the target value is
-
reached quickly and
-
with minimum overshooting
when the setpoints and actual values are changed.
The differential component K
D
(C072) is usually not required for pressure and flow-rate controls
(set C072 = 0).
Guide values for pressure control and flow rate
Code
Gases
Liquids
C070 (V
P
)
0.1
0.02 ... 0.1
C071
(T
n
)
5000
(5 s)
200 ... 1000
(0.2 s ... 1 s)