C.4.5 checking the data, C.4.5, Checking the data – Festo Контроллеры двигателя SFC-LAC User Manual
Page 377: C−51

C. Object directory DS402 and CI
C−51
Festo GDCP−SFC−LACI−CO−EN en 0812NH
C.4.5
Checking the data
Permitted value ranges
Transferred parameters and values are checked by the
SFC−LACI before being accepted.
Note
In the case of invalid parameters or values, an error mes−
sage will not appear in the response; rather, the received
value will always be returned (Echo).
Recommendation:
Check that values have been written correctly by downloadĆ
ing the current contents of the object with a subsequent Read
command. The higher level controller must compare the sent
command with the Echo" from the SFC−LACI and check the
checksum.
Note
The following applies when writing the objects:
Ĉ Discrete values (values from a value list):
an invalid value will not be accepted; the previously
valid value will be retained.
Ĉ Continuous values (e.g. lengths, speeds, etc.): an imperĆ
missible value will be limited to the nearest permitted
value.
Error messages
If there are errors in the commands (e.g. syntax errors, transĆ
mission errors), the value <0x00FF> will be transmitted
(object 2FF0h) instead of the usual reply. Possible causes:
ć
Incorrect initial character, separating character or empty
character
ć
Incorrect hex digit
ć
Incorrect value type