6

Diagnostics

96

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

Table of error messages

22h

Homing

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Homing run to switch unsuccessful. A corresponding switch has not been found.

Check to make sure the correct homing method is set.

Check to see if the limit switches and/or homing switches are connected and if they have been

parameterised correctly (normally closed contact/normally open contact?). Check the func-

tionality of the switches and check the lines for wire break.

If the error is still present, it means there is an internal defect and the device has to be replaced.

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

B, C, E, F

23h

No index pulse found

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Error during homing: no zero pulse found. Encoder defective or incorrect parameterisation of the

encoder resolution.

Check the output signals of the encoder, in particular the index signal.

Check the parameterisation of the encoder resolution.

Acknowledgement option: Cannot be acknowledged, software reset required.

Parameterisable error response(s):

B, C, E, F

24h

Drive function is not supported in operated mode

Can be parameterised as:

E/W/-

Diagnostic memory: optional

Function is not supported in this mode. The request has been ignored.

Change the operating mode or select a different drive function.

For parameterisation as an error: The error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

E, F

For parameterisation as a warning: The warning disappears if a switch is made to a valid drive

function.

25h

Path calculation

Can be parameterised as:

E/-/-

Diagnostic memory: optional

The positioning target cannot be reached through the positioning or edge condition options.

For record linking: The end speed of the last record was higher than the target speed of the following

record.

Check the parameterisation of the affected records.

Also check the actual values of the previous positioning process at the switching point, if neces-

sary, by using the trace function. The error may be caused by the actual velocity or the actual

acceleration being too high at the switching point.

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s): A