6

Diagnostics

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

91

Table of error messages

01h

Software error

Can be parameterised as:

E/-/-

Diagnostic memory: always

An internal firmware error has been detected.

Contact Festo Service.

Acknowledgement option: Cannot be acknowledged, software reset required.

Parameterisable error response(s): A

02h

Default parameter file invalid

Can be parameterised as:

E/-/-

Diagnostic memory: always

An error has been detected when examining the default parameter file. The file is damaged.

Reload the default parameter file into the device via a firmware update. If the error is still present,

it means the memory may be faulty and the device needs to be replaced.

Acknowledgement option: Cannot be acknowledged, software reset required.

Parameterisable error response(s): A

05h

Zero angle determination

Can be parameterised as:

E/-/-

Diagnostic memory: always

The rotor position could not be clearly identified. The commutation point is invalid.

The drive is blocked: Ensure freedom of movement.

Excessively high load: Reduce load.

The axis is not fastened stiffly enough: Stiffen the axis mounting.

The effective load is not fastened stiffly enough on the axis: Stiffen the connection.

Effective load can vibrate: Form a stiffer load; modify the natural frequency of the load.

If several drives are fitted in a system that can vibrate: Carry out commutation point search one

after the other.

Controller parameters have been set incorrectly: Determine the controller parameters and set the

correct value. To do this, you may have to perform a commutation point search without a load

(remove the load, correctly set the tool mass and applied load), start the axis, connect the load

(correctly set the tool mass and applied load), determine the new controller parameters (see FCT

help on controller parameterisation), reparameterise the drive and then restart the commutation

point search with new controller parameters.

This error can also occur if the set motor current is too low to move the shaft and any possible

load. Correct the settings for the motor current if necessary.

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s): A

06h

Encoder

Can be parameterised as:

E/-/-

Diagnostic memory: always

An error has occurred during evaluation of the encoder. The current position values may be incorrect.

Conduct a software reset with a commutation angle search and homing procedure.

Acknowledgement option: Cannot be acknowledged, software reset required.

Parameterisable error response(s): A