Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English
Table of error messages
38h
Parameter file access
Can be parameterised as:
E/-/-
Diagnostic memory: optional
During a parameter file procedure all other reading and writing routines for the parameter file are
blocked.
•
Wait until the process is complete. The time between two parameter file downloads should not
fall below 3 seconds.
–
Acknowledgement option: Error can be acknowledged.
Parameterisable error response(s): G
39h
Trace warning
Can be parameterised as: -/
W/-
Diagnostic memory: optional
An error has occurred during trace recording.
•
Start a new trace recording.
–
For parameterisation as a warning: The warning disappears if a new trace has been started.
3Ah
Homing Timeout
Can be parameterised as:
E/-/-
Diagnostic memory: optional
Error during homing process in controlled operation. The switch has not been found within a certain
time.
•
Check the switch configuration and the electric connection of the switch(es).
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s):
B, C, E, F
3Bh
Homing method invalid
Can be parameterised as:
E/-/-
Diagnostic memory: optional
Homing error. A homing method block has been set, for example, in open-loop operation.
•
Select a permissible homing method.
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s):
E, F
3Ch
Two edges in one cycle
Can be parameterised as:
E/-/-
Diagnostic memory: optional
Two input signals have been set in the valve type in one input read cycle.
•
Programme the PLC so that two records (or a record and homing run) are not started in a cycle.
A minimum time delay of 2 ms must be maintained between two edges. In the event of manual
control, only one switch should be operated after the other.
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s):
B, C, E, F
3Dh
Start-up event
Can be parameterised as: -/-/
I
Diagnostic memory: always
The controller has been switched on or was switched on for longer than 48 days. This event also
occurs when deleting the diagnostic memory. The start-up event does not occur if the preceding entry
in the diagnostic memory has already been a start-up event.
•
This event is only used for improved documentation of the malfunctions.