Diagnostics

100

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

Table of error messages

38h

Parameter file access

Can be parameterised as:

E/-/-

Diagnostic memory: optional

During a parameter file procedure all other reading and writing routines for the parameter file are

blocked.

Wait until the process is complete. The time between two parameter file downloads should not

fall below 3 seconds.

Acknowledgement option: Error can be acknowledged.

Parameterisable error response(s): G

39h

Trace warning

Can be parameterised as: -/

W/-

Diagnostic memory: optional

An error has occurred during trace recording.

Start a new trace recording.

For parameterisation as a warning: The warning disappears if a new trace has been started.

3Ah

Homing Timeout

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Error during homing process in controlled operation. The switch has not been found within a certain

time.

Check the switch configuration and the electric connection of the switch(es).

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

B, C, E, F

3Bh

Homing method invalid

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Homing error. A homing method block has been set, for example, in open-loop operation.

Select a permissible homing method.

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

E, F

3Ch

Two edges in one cycle

Can be parameterised as:

E/-/-

Diagnostic memory: optional

Two input signals have been set in the valve type in one input read cycle.

Programme the PLC so that two records (or a record and homing run) are not started in a cycle.

A minimum time delay of 2 ms must be maintained between two edges. In the event of manual

control, only one switch should be operated after the other.

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s):

B, C, E, F

3Dh

Start-up event

Can be parameterised as: -/-/

I

Diagnostic memory: always

The controller has been switched on or was switched on for longer than 48 days. This event also

occurs when deleting the diagnostic memory. The start-up event does not occur if the preceding entry

in the diagnostic memory has already been a start-up event.

This event is only used for improved documentation of the malfunctions.