Table of error messages
3Eh
Diagnostic memory
Can be parameterised as:
E/-/-
Diagnostic memory: always
An error has occurred when writing or reading from the diagnostic memory.
•
Acknowledge the error. If the error is still present, it means a memory module is probably
defective or an incorrect entry has been stored.
•
Erase the diagnostic memory. If the error still occurs, the controller must be replaced.
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s): G
3Fh
Record invalid
Can be parameterised as:
E/-/-
Diagnostic memory: optional
The started record is invalid. The record data is implausible or the record type is invalid.
•
Check the record parameters.
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s): B, C, D,
E, F, G
40h
Last Teaching not successful
Can be parameterised as: -/
W/I
Diagnostic memory: optional
Teaching of the current positioning record is not possible.
•
The current positioning record must be of the type “position record”.
–
For parameterisation as a warning: The warning disappears if the following Teach test is success-
ful or a switch takes place from the Teach mode (mode 1) to normal operation (mode 0).
41h
System reset
Can be parameterised as:
E/-/-
Diagnostic memory: always
An internal firmware error has been detected.
•
Contact Festo Service.
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s): A
43h
FCT connection without master control
Can be parameterised as: -/
W/I
Diagnostic memory: optional
There is no longer a connection to the FCT, e.g. the cable was disconnected.
•
Check the connection and perform a reset if necessary.
–
For parameterisation as a warning: The warning disappears if the connection to the FCT is
re-established.