Table of error messages
14h
Negative direction locked
Can be parameterised as:
E/-/-
Diagnostic memory: optional
A limit switch error or a software limit position error has occurred and subsequently a movement in
the blocked direction has been initiated.
•
Check the target data.
•
Check positioning area.
•
This error can only be acknowledged if the drive is within the valid movement range. If necessary,
start a corresponding position set or move the drive by using the jog function. Movements in a
negative direction are blocked.
–
Acknowledgement option: Error can only be acknowledged after eliminating the cause.
Parameterisable error response(s): A,
B, C, E, F
15h
Output stage temperature exceeded
Can be parameterised as:
E/-/-
Diagnostic memory: optional
The permissible limit value for the output stage temperature has been exceeded. The output stage is
possibly overloaded.
•
This error can only be acknowledged if the temperature is within the permissible range.
•
Check cylinder sizing.
•
Check motor and cabling for short circuits.
•
Check the mechanics for sluggishness.
•
Reduce the ambient temperature, improve heat dissipation.
–
Acknowledgement option: Error can be acknowledged.
Parameterisable error response(s): A, B,
C, D
16h
Output stage temperature too low
Can be parameterised as:
E/-/-
Diagnostic memory: optional
The ambient temperature is below the permissible range.
•
Increase the ambient temperature. This error can only be acknowledged if the temperature is
within the permissible range.
–
Acknowledgement option: Error can be acknowledged.
Parameterisable error response(s): A, B,
C, D
17h
Logic voltage exceeded
Can be parameterised as:
E/-/-
Diagnostic memory: optional
The logic power supply monitor has detected an overvoltage. This is either due to an internal defect
or an excessive supply voltage.
•
Check external supply voltage directly on the device.
•
If the error is still present after a reset has been conducted, it means there is an internal defect
and the device has to be replaced.
–
Acknowledgement option: Error can be acknowledged.
Parameterisable error response(s): A,
B