5

Commissioning

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

57

Valve profile: Outputs

Output

Designation

Description

1

Position 1 reached

The target position of the respective position record has been

reached.

2

Position 2 reached

3 … 6

7

Position 7 reached

8

In Zone

(

section 5.9.1)

The drive is located within the position zone of the active position

record parameterised in FCT. The position zone is formed by the

position comparators.

If the input is inactive, output 8 remains set. If, however, the drive

is pushed out of position and then returns, the output remains

inactive.

If another input is active, then the current position is compared

to its position zone and output 8 is set again depending on the

result.

9

Referenced

After a successful homing run this output is set and remains set

for as long as the drive is referenced.

10

Ready

Drive is ready for operation. All requirements for starting a

position record are fulfilled (e.g. load voltage is present, ENABLE

is set, no serious error).

11

Torque Limit reached

The parameterised torque/force limit has been reached.

Tab. 5.4

Valve profile: Assignment of outputs

Electrical specification of the inputs and outputs:

section 4.4.1.