B

Control via Ethernet (CVE)

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

127

#4

Lock higher-order control

System

UINT08

R/W1/W2/-/-

0x00

The master control is not blocked. The higher-order controller can be changed by all

interfaces.

0x01

The master control is blocked. Before the higher-order controller can be changed again,

this block has to be removed again. Only the interface that has the higher-order controller at the time

can do this.

Values: 0 … 1

Default: 0

#31

Record number preselection

Record

UINT08

R/W1/W2/-/-

Number of the preselected positioning record. At the controller interface, a new positioning record

can already be preselected while an old one is still active. Note: The active positioning record is in

object #141

Record 1 … xx

normal records

Values: 1 … 31

#57

Actual speed

System

SINT32

R/-/-/-/-

Current actual velocity

Unit: SINC/s

Values: –2147483648 … 2147483647

Default: 0

#58

Actual current

System

SINT32

R/-/-/-/-

Current motor current

Unit: mA

Values: –2147483648 … 2147483647

Default: 1

#59

Actual force

System

SINT16

R/-/-/-/-

Current actual force in one-tenth of one percent of the maximum motor current (calculated from the

measured current)

Unit: ‰

Values: –32768 … 32767 Default: 0