5

Commissioning

40

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

Note

The CMMO-ST does not carry out any positioning jobs/records if it is not referenced.

Carry out a homing run in the following cases to anchor the measuring reference

system to the reference point:

every time the logic voltage supply is switched on or after every failure

after changing the homing method, the axis zero point, the direction of rotation

or the encoder resolution

Note

If the axis zero point is modified:

Existing software end positions and the target positions in the record table will be

shifted together with the axis zero point.

Adjust the software end positions and the target positions if necessary.

Note

Damage to components when the permissible impact pulse is exceeded.

Operate the drive only with the permissible load (

operating instructions for the

drive).

If necessary, limit the maximum current (motor force) when travelling to the stop.

Note

Interruption of ongoing tasks due to inadequate load voltage supply.

Make sure that the tolerance of the load voltage supply can be maintained at full

load directly on the voltage terminal of the CMMO-ST (

section 4.2).