6

Diagnostics

92

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

Table of error messages

09h

Offset determination for current measurement

Can be parameterised as:

E/-/-

Diagnostic memory: always

An error has occurred during initialisation of the current measurement.

Perform a software reset.

Acknowledgement option: Cannot be acknowledged, software reset required.

Parameterisable error response(s): A

0Bh

Parameter file invalid

Can be parameterised as:

E/-/-

Diagnostic memory: always

No valid parameter set stored. After creation of the parameter file, a firmware update is performed, if

necessary: as much data as possible is automatically taken from the parameter file. Parameters that

are not initialised through the parameter file are taken over from the default parameter file.

Enter a valid parameter set in the device. If the error is still present, the hardware may be defect-

ive.

Acknowledgement option: Error can only be acknowledged after eliminating the cause.

Parameterisable error response(s): A

0Ch

Firmware update execution error

Can be parameterised as:

E/-/-

Diagnostic memory: optional

The firmware update has not been properly executed/completed.

Check the Ethernet connection between the controller and PC and run the firmware update again.

The previous firmware version remains active until successful completion of the firmware update.

If this error is still present, the hardware may be defective.

Acknowledgement option: Cannot be acknowledged, software reset required.

Parameterisable error response(s): A

0Dh

Overcurrent

Can be parameterised as:

E/-/-

Diagnostic memory: always

Short circuit in the motor, in the lines or in the brake chopper.

Output stage defective.

Incorrect parameterisation of the current regulator.

Error message immediately after connecting to the load supply: Short circuit in the output stage.

The controller must be replaced.

Error message only occurs during setting of the output stage enable: - Disconnect the motor plug

directly on the controller; if the error still occurs, the controller must be replaced.- If the error only

occurs when the motor cable is connected, check the motor and cable for short circuits, e.g. with

a multimeter.

Check parameterisation of the current regulator. An incorrectly parameterised current regulator

can generate currents up to the short-circuit limit; as a rule this is clearly noticeable through high

frequency whistling. Inspection with the trace function in FCT (active current actual value).

Acknowledgement option: Cannot be acknowledged, software reset required.

Parameterisable error response(s): A