Commissioning

Festo – GDCP-CMMO-ST-EA-SY-EN – 1301a – English

65

Requirements

Drive is referenced and ready.

Start record 1

Record 1 is started by setting input Pos1.

Error

An error occurs, e.g. a following error. In this example, this malfunction has been parameterised as an

error and, as a response, a deceleration is effected with the quick stop ramp (Quick stop).

The Ready output is reset.

The drive brakes with the quick stop ramp and remains stationary.

Acknowledge error

The error is acknowledged by setting the RESET input. After setting this input the parameterised time

for the switch-on delay of the holding brake starts to run. When this time has expired the Ready output

is set again.

Restart record 1

When the input Pos1 has been reset, record 1 can be restarted by setting this input again.

Destination 1 reached

After the parameterised target position window is reached and the parameterised damping time has

expired, the output OnPos1 is set.