FEC FUSION Operations Manual
Chapter 4: System Setup and Wiring (Rev. 2.1)
Page 4-49
DeviceNet Specifications
Speed
125K, 250K and 500K baud
Nodes
64
Maximum Distance
500 meters at 125K baud
250 meters at 250K baud
100 meters at 500K baud
Cable
Twisted
pair for signal and power
Allen Bradley or equivalent ;
Thin Cable #1485C-P1-C
Thick Cable # 1485C-P1-A
Communications Type
Master/Slave
Interface Board Specifications
Operating Voltage
+5V, 200 ma
Output data bytes
512 max.*
Input data bytes
512 max.*
Servers per group
2 Maximum
Interface type
Dual Port RAM or Serial Interface
* Actual FUSION Configuration is 16 Bytes of OUTPUTS (128 points) and 4 Bytes of INPUTS
(32 points). (See DeviceNet Signal Reference at the end of this chapter for I/O Signal map)
EDS File
Each device on a DeviceNet network is associated with an EDS file containing all necessary
information about the device to be connected. The network configuration program uses this
file during configuration of the network.
The EDS file associated with the FEC device can be downloaded from the FEC website sup-
port & downloads pages. www.fec-usa.com (file: abs.eds)
(the file can also be downloaded directly from HMS - www.hms.se)
Note: The FEC system will appear in the network Vendor list as “HMS Fieldbus Systems” and
in the network as “Anybus-S DeviceNet” adapter. This is the manufacturer of the interface
board which is integrated into the Multi-2 Unit
.