Chapter 4: System Setup and Wiring
Page 4-40
Termination
Termination of the fieldbus requires a terminating resistor at each end of the fieldbus. A ter-
mination switch is provided on the Profibus-DP interface board. Set the switch to “ON”, if
termination is required. If external terminators are used, the switch must be in the off posi-
tion.
GSD File
Each device on a Profibus network is associated with a GSD file containing all necessary in-
formation about the device to be connected. The network configuration program uses this file
during configuration of the network.
The GSD file associated with the FEC device can be downloaded from the FEC website.
www.fec-usa.com
(See Support/Download area) (File : hms_1003.gsd)
(the file can also be downloaded directly from HMS - www.hms.se)
Profibus Specifications
Speed
9.6K - 12M baud – auto-selected
Nodes
126 Note: Node 126 is reserved for
commissioning purposes only
Distance
200m max. at 1.5Mbit/s extendable with
repeaters.
Cable
Shielded Copper Twisted Pair or fiber
optic
Communications Type
Master/Slave - EIA RS485
Protocol Version
Ver. 1.10
Maximum Cyclic I/O Size
244bytes In, 244 bytes out max.
416 total bytes max.
Data transmission
The module only supports cyclic I/O da-
ta transmission.
Note: Limited Coded Binary Integer da-
ta is sent in the cyclic I/O data
Profibus connector - D-Sub
Pin 1
Not Connected
Pin 2
Not Connected
Pin 3
B- Line
Positive RxD/TxD accord-
ing to RS485 Spec.
Pin 4
RTS
Request to send
Pin 5
GND Bus
Isolated GND from RS
485 side
Pin 6
+5V Bus
Isolated +5V from RS 485
side
Pin 7
Not connected
Pin 8
A- Line
Negative RxD/TxD ac-
cording to RS485 Spec.
Pin 9
Not Connected
Housing
Shield
Connected to PE