FEC FUSIONE-HS-2 User Manual
Page 171

FUSION Operations Manual
9.2
Torque Transducer Abnormals
Calibration Error
When the CAL switch is pressed
preset value is missing or a wrong tool is connected
RECOVERY:
1. Program correct Full Scale Preset value for the tool connected
2. Exchange tool cable, tool and/or co
system after each exchange, and make note of any change in the location of the a
normal.
3. Replace the defective component.
9.2.1
Code 1-0 TORQUE TRANSDUCER / ZERO VOLTAGE ERROR
Zero level does not match
tion.
This abnormal is caused from;
1. When the tool transducer is sensing excessive torque due to pressure on the tool body.
2. If the controller or the transducer cable is located in an elect
3. When the torque transducer,
RECOVERY:
1. Check that the tool has no
has occurred with the tool assembly)
2. Verify that the cable or
sources. Relocate as required and reinitialize.
3. Exchange tool cable, tool and/or controller with known working units. Reinitialize the sy
tem after each exchange, a
4. Replace the defective component.
9.2.2
Code 1-1 TORQUE TRANSDUCER / CAL VOLTAGE ERROR
Calibration voltage error during power on initialization.
This abnormal is caused from;
1. When the tool transducer is sensing excessive torque due to pressure on the tool body.
2. If the controller or the transducer cable is located in an electric or magnetic noise field.
3. When the torque transducer,
RECOVERY:
1. Check that the tool has no signs of an external force being applied to it. (No heavy impact
has occurred with the tool assembly)
2. Verify that the cable or
sources. Relocate a
3. Exchange tool cable,
tem after each exchange, and make note of any change in the location of the abnormal.
4. Replace the defective component.
FUSION Operations Manual Chapter 9: Troubleshooting (Rev. 2)
Page 9-3
Torque Transducer Abnormals
CAL switch is pressed on the Fusion front panel, "
E
" is shown if the FULL
preset value is missing or a wrong tool is connected.
Program correct Full Scale Preset value for the tool connected
Exchange tool cable, tool and/or controller with known working units. Reinitialize the
system after each exchange, and make note of any change in the location of the a
Replace the defective component.
0 TORQUE TRANSDUCER / ZERO VOLTAGE ERROR
Zero level does not match master level read from tool EEPROM during power on initializ
This abnormal is caused from;
1. When the tool transducer is sensing excessive torque due to pressure on the tool body.
2. If the controller or the transducer cable is located in an electric or magnetic noise field.
3. When the torque transducer, Tool cable or the controller malfunctions.
1. Check that the tool has no signs of an external force being applied to it. (
the tool assembly)
fy that the cable or controller is not located near any high voltage transient power
sources. Relocate as required and reinitialize.
cable, tool and/or controller with known working units. Reinitialize the sy
tem after each exchange, and make note of any change in the location of the abnormal.
4. Replace the defective component.
1 TORQUE TRANSDUCER / CAL VOLTAGE ERROR
Calibration voltage error during power on initialization.
This abnormal is caused from;
transducer is sensing excessive torque due to pressure on the tool body.
2. If the controller or the transducer cable is located in an electric or magnetic noise field.
3. When the torque transducer, Tool cable or the controller malfunctions.
1. Check that the tool has no signs of an external force being applied to it. (No heavy impact
has occurred with the tool assembly)
2. Verify that the cable or controller is not located near any high voltage transient power
sources. Relocate as required and reinitialize.
Exchange tool cable, tool and/or controller with known working units. Reinitialize the sy
tem after each exchange, and make note of any change in the location of the abnormal.
4. Replace the defective component.
Chapter 9: Troubleshooting (Rev. 2)
" is shown if the FULL-SCALE
ntroller with known working units. Reinitialize the
system after each exchange, and make note of any change in the location of the ab-
0 TORQUE TRANSDUCER / ZERO VOLTAGE ERROR
master level read from tool EEPROM during power on initializa-
1. When the tool transducer is sensing excessive torque due to pressure on the tool body.
ric or magnetic noise field.
or the controller malfunctions.
applied to it. (No heavy impact
not located near any high voltage transient power
cable, tool and/or controller with known working units. Reinitialize the sys-
nd make note of any change in the location of the abnormal.
transducer is sensing excessive torque due to pressure on the tool body.
2. If the controller or the transducer cable is located in an electric or magnetic noise field.
or the controller malfunctions.
1. Check that the tool has no signs of an external force being applied to it. (No heavy impact
not located near any high voltage transient power
tool and/or controller with known working units. Reinitialize the sys-
tem after each exchange, and make note of any change in the location of the abnormal.