FEC FUSION Operations Manual
Chapter 4: System Setup and Wiring (Rev. 2.1)
Page 4-41
Profibus Status LED
Status LEDs
Fieldbus Diagnostics
Red
Indicates faults on fieldbus side
LED #4
Flashing Red -
1sec
Config. Error - in/out length set
at module initialization does not
match length in network config.
Flashing Red -
2sec
Error in user parameter data -
parameter length/content does
not match network
length/content
Flashing Red -
4sec
Error in initialization of Profibus
communication ASIC
On-Line
LED #2
Off
Module not online
Green
Module online and communica-
tion OK
Off- Line
LED #3
Off
Module is not offline
Red
Module is offline on the fieldbus
Note: LED #1- Not Used
Node Address
Before configuring the Profibus-DP module the node address has to be set. This is done with
two rotary switches on the module which can set the node address 1-99 in decimal format.
The Upper rotary switch (closest to the D-sub) sets the “ten” digit (X 10), and the bottom rota-
ry switch sets the single digit. Example: To set node 37, place the “ten” switch on 3, and the
single digit switch on 7.
This switch must be set before power is on, and cannot be changed during operation.
Configuration
FEC Profibus I/O is pre-configured according to the I/O Signal Map (See below). Configura-
tion of the Profibus Master MUST match the configuration of the FEC Profibus slave. In the
Profibus Master set-up, input size and output size is set as “byte” ordering. (Do not use
“word” ordering. This will inverse the I/O location) When setting the Profibus Master configu-
ration, PLC input size refers to FEC output size (ie. Accept, Reject, Busy, etc.) and PLC out-
put size refers to FEC inputs (ie. Start, Stop, Reset, etc.). FEC will show up as 2 modules.
Module 1 is inputs, module 2 is outputs.