11. Monitor
164
In the case of the X-SEL-R/S, RX/SX or RXD/SXD controller, the header of the time of error column
displayed as part of detailed error information becomes "Data (time the error occurred)" instead of "After
Reset (elapsed time after the reset)."
Fig. 11.19 Detailed Error Information (When the XSEL-R/S, RX/SX and RXD/SXD controllers’ calendar
function is used)
(Note) If date & time data is lost, the following error occurs. In this case, the date & time data becomes
2000/01/01 00:00:00.
Fig. 11.20 Error Display
(Note) Refer to 15.4, "Setting Time" for how to set the internal clock of the controller.
(Note) When bits 0 to 3 of Other parameter No. 47, "Other setting bit pattern 2" are set to 2, (Do not use
the calendar function (use the elapsed time after the reset)), the header of the time of error
column becomes "After Reset (elapsed time after the reset)."
(The factory default for bits 0 to 3 of Other parameter No. 47, "Other setting bit pattern 2" is 1
(Use the calendar function).)