Page 61
Remote Terminal Setup
Component Power-up and Configuration
1
Take the printer offline by pressing SELECT. The SELECT light should go off.
2
Position the print head at the top of the paper and press the TOF SET button.
3
Put the printer back online by pressing SELECT. The SELECT light should go on.
4
Press the MODE button until the light next to HSD is lit.
5
Press the PITCH button until the light next to 17 is lit.
Note: Pitch may be set to a lower number (resulting in larger print) if transactions are less
than 132 characters.
Remote Terminal Setup
The CFN remote port can be directly connected to a terminal. The terminal supplied by
GASBOY is a Link MC5 CRT terminal. If your site uses a remote terminal, install and
complete the setup of the terminal as specified in the manufacturer’s setup instructions. The
baud rate and emulation mode must be set to match the SC configuration.
SC Configuration Changes
Although the system has already been configured and tested at the factory, you may need to
perform some configuration changes to match the site’s characteristics. Follow the instructions
in the SC III Configuration Manual to make these changes.
The software for a CFN system with a 3-1/2” disk drive and a hard disk is supplied on the hard
disk and also on two backup 3-1/2” diskettes. During normal system use, any configuration
changes that you add to the CFN system are automatically place on the hard disk. To keep
your backup current, these changes must be copied onto the 3-1/2” backup diskette labeled
DISK #1.
SW2-4
ON
DSR output signal: Active
SW2-5
ON
Buffer threshold: 32 bytes
SW2-6
OFF
Busy signal timing: 1 second (minimum)
SW2-7
ON
DTR signal: Space after power on
SW2-8
OFF
Not used