System Power

Page 54 MDE-4793A CFN Series Site Controller III Start-up Manual for CFN III Versions 3.5 and above · November 2008

4

On the specified locations of the following components, use a digital AC voltmeter to test and
record the voltages as follows:

• Optional power conditioner - on the output receptacle (see

Figure 7-1

)

• AC surge protector strip - on the output receptacle (see

Figure 7-1

)

• PCU(s) - at TB202
• ICR(s) - at TB6

Figure 7-1: AC Output Receptacle

N
(neutral)

G
(ground)

H
(hot)

Measure

Range

From

To

Hot

Neutral

Measure AC voltage between the H and N screws.
This voltage should be 120 VAC ± 10 percent (108 VAC to 132 VAC).

Hot

Ground

Measure AC voltage between the H and G screws.
This voltage should be 120 VAC ± 10 percent (108 VAC to 132 VAC).

Neutral

Ground

Measure AC voltage between the N and G screws.
This voltage should be 0 VAC ± 1 volt.

Note: If power is not within these specifications, correct it before you continue.