MDE-4793A CFN Series Site Controller III Start-up Manual for CFN III Versions 3.5 and above · November 2008

Page 35

PPC or SC III/POS WS (Optional)

Physical System Layout

PPC or SC III/POS WS (Optional)

1

Verify if the Profit Point and any optional equipment is located in an office type environment
and is correctly installed according to the SC III Installation Manual.

2

Verify if the AC power cord for the Profit Point is directly connected to the output of the AC
Surge Protector Strip (C01218).

3

The RS-485 converter must be installed as described below. If you are locating the Profit Point
more than eight feet from the SC, you must use two additional RS-485 junction boxes to
connect the devices.

A modular cable must be directly connected to the modular jack port on the back of the SC
labeled LOOP 3. The other end of the modular cable is connected to one of the modular jacks
on the converter. The converter is connected to the Profit Point port SERIAL1 via a 25-pin to
9-pin cable. The converter power supply must be plugged into the same AC Surge Protector
Strip (C01218) as the Profit Point.

POS Distribution Box (POS D-Box) is connected via a 9-pin cable from the Serial2 port on
the Profit Point (COM2 on the SCIII/POS WS) to the Serial2 port on the D-Box. If the site
has a PIN Pad, the Serial3 port of the Profit Point (COM3 on the SCIII/POS WS) will be
connected to the Serial3 port of the D-Box. The D-Box power supply must be plugged into the
same AC Surge Protector Strip (C01218) as the Profit Point.

“Old” CASH DRAWER is connected via a 9-pin D-type connector from the cash drawer to
the CASH DRAWER port on the back of the POS D-Box. “New” CASH DRAWER is
connected connects to the receipt printer which connects to the minitower’s 4-port fan-out
cable.

CUSTOMER DISPLAY must be installed according to the Profit Point Installation Manual.
Verify if the Customer Display is connected to the 9-pin CUSTOMER DISPLAY port on the
POS D-Box.

4

Optional equipment connection:

RECEIPT PRINTER connection depends upon the type of receipt printer ordered. For a
parallel printer, the printer cable is connected to the D-type 25-pin female connector
PRINTER on the back of the Profit Point (LPT1 on SC III/POS WS). For an RS-485 printer,
the modular cable is connected directly into the RS-485 jack on the converter. The receipt
printer must be plugged into the same AC Surge Protector Strip as the Profit Point.

PIN PAD must be installed as per instructions in MDE-4299 CFN Series Profit Point
Installation Manual
. Verify if the PIN pad is securely connected to the PIN PAD port located
on the POS D-Box.

SCANNER must be installed as per instructions in MDE-4299 Profit Point Installation
Manual
. Verify if the scanner is securely connected to the 9-pin SCANNER port located on
the POS D-Box. If a scanner is used that needs external power, it must be plugged into the
same AC Surge Protector Strip as the Profit Point.