SC COMM CPU PCB
Jumpers and Switch Settings
6 – Jumpers and Switch Settings
This section covers the jumper and switch settings for the various components of your SC III
system.
Jumpers and switch settings must be set properly to ensure correct operation.
IMPORTANT INFORMATION
SC COMM CPU PCB
Figure 6-1: SC III Comm CPU Board
Jumpers, K3 to K12
Jumper
Function
Setting
K3
AC power fail sense
2 - 3 to enable
1 - 2 to disable
K4
AC watchdog timer
1 - 2 to enable
K5
SC - Comm CPU (testing only)
1 - 2 to reset
K6
RS-485 loop 1, 2 to 4 wire
2 - 3 for 4 wire
1 - 2 for 2 wire