beautypg.com

Dip switches – Gasboy CFN Series Site Controller III Start-up User Manual

Page 53

background image

MDE-4793A CFN Series Site Controller III Start-up Manual for CFN III Versions 3.5 and above · November 2008

Page 47

ICR

Jumpers and Switch Settings

ICR

DIP Switches

The ICR has an S2 bank of 10 Dual Inline Package (DIP) switches. Switches 1 through 6
provide functional settings; switches 7 through 10 are address settings. The settings and
functions are shown in the following tables.

ICR Software

Switch

Function

S2-1

No function

S2-2

DPT

Open = enables decimal point on the keypad.
Closed = the decimal point acts as a CLEAR key.

S2-3

DIS

Open = two lines of display are displayed.
Closed = only one line of display is displayed.

S2-4

INSRT

Open = insertion magnetic card reader.
Closed = swipe magnetic card reader or optical reader.

S2-5

GATE

Open = ICR.
Closed = gate controller.

S2-6

OPT

Open = optical reader.
Closed = magnetic card reader.

An address must be set up to identify the ICR. This address is a unique identifier for when
multiple ICRs are connected on the same RS-485 line. Up to 16 units can be used on the same
line (there are 16 addresses). Addressing should start at 1 and continue sequentially through
16. The physical wiring order does not have to correspond with the address order (the first unit
on the RS-485 line does not have to be address 1). The chart below gives the switch setting for
the address selections.
Note: The standalone receipt printer (when used) is addressed as an ICR; ensure that you use

an address different from any ICR.

Address

S2-7

S2-8

S2-9

S2-10

Address

S2-7

S2-8

S2-9

S2-10

ADDR4

ADDR3

ADDR2

ADDR1

ADDR4

ADDR3

ADDR2

ADDR1

1

Closed

Closed

Closed

Closed

9

Open

Closed

Closed

Closed

2

Closed

Closed

Closed

Open

10

Open

Closed

Closed

Open

3

Closed

Closed

Open

Closed

11

Open

Closed

Open

Closed

4

Closed

Closed

Open

Open

12

Open

Closed

Open

Open

5

Closed

Open

Closed

Closed

13

Open

Open

Closed

Closed

6

Closed

Open

Closed

Open

14

Open

Open

Closed

Open

7

Closed

Open

Open

Closed

15

Open

Open

Open

Closed

8

Closed

Open

Open

Open

16

Open

Open

Open

Open

An S3 switch enables the diagnostic mode of the ICR. Diagnostic mode is enabled when the
switch is in the down position.

Switch

Function

S3

Up = normal; Down = test mode

This manual is related to the following products: