User Manual

214

i Series / iX Series

9.5 Mode iX Option

9.5.1 Introduction

This section contains information on the installation and operation of the Mode-iX phase mode
controller to be used with the California Instruments iX-series of power sources.

GENERAL DESCRIPTION

The Mode-iX phase mode controller accepts three outputs from California Instruments iX-series
power systems and directs them to one output for a single phase system or three outputs for a
three phase system. This switching action is performed automatically via a control signal from
the power system to the Mode-iX phase mode controller.

9.5.2 Specifications

9.5.2.1 Input

Line Voltage
(user configurable)

115 VAC ±10%

230 VAC ±10%

Line Current

< 0.25 amps at 115 VAC input

< 0.125 amps at 230 VAC input

Line Frequency

47 to 63 Hz

Fuse Rating

0.25 amp, slow acting at 115 VAC input

0.125 amp, slow acting at 230 VAC input

9.5.2.2 Phase Mode Terminals

Voltage

300 volts line to chassis

600 volts line to line

Current

37A rms, SOURCE A, B, C, N

37A rms, LOAD B, C

112A rms, LOAD A, N

9.5.2.3 Controls/Indicators

ON/OFF toggle switch

Phase mode push button switch

Power lamp

One Phase Mode lamp

Three Phase Mode lamp