Specifications – AMETEK i Series User Manual
Page 16

User Manual
2
i Series / iX Series
2. Specifications
All specifications are for a single i or iX series chassis and 25 5 C sine wave output with a
resistive load unless noted otherwise.
2.1 Electrical
2.1.1 Input
Parameter
3001i & Ix
5001i & iX
Line Voltage:
208-240 10% VAC, single phase
208-240 V
LL
10%, (Standard)
400-440 V
LL
10%, (-400)
400-480 V
LL
10%, (-400)
3 phase, 3 wire + ground
Line VA:
5000VA
8000VA
Line Current:
25 A RMS max. (Per Box)
23 A RMS max. at 208-240 VAC
12 A RMS max. at 400-440 VAC
and 400-480 VAC (Per Box)
Line Frequency:
50-60 Hz 10%
Efficiency:
80% (typical) depending on line and load
Power Factor:
0.7 (typical)
0.9 (typical)
Inrush Current:
100 A
pk
for 100 s
100 A
pk
for 100 s at 208-240V
50 A
pk
for 100 s at 400-440 VAC
and 400-480 VAC
Hold-Up Time:
15 ms
Isolation Voltage:
2200 VAC input to output
1350 VAC input to chassis