AMETEK i Series User Manual

Page 157

background image

User Manual

i Series / iX Series

143

VOLT FREQ MIN

Standard/Group

RTCA

Group1

Group2

Group3

Voltage

100

104

104

104

101.5

105.5

105.5

105.5

Frequency

360

360

360

360

Table 9-7: Emergency Voltage and Frequency Minimum

Standard/Group

RTCA

Group1

Group2

Group3

Voltage

122

122

122

122

120.5

120.5

120.5

120.5

Frequency

440

440

650

800

Table 9-8: Emergency Voltage and Frequency Maximum

This test is test will set the voltage and frequency for a level defined by Table 9-7. The test will
last for 30 minutes. The test will be repeated using the voltage from Table 9-8 and frequency
from Table 9-7. The

key (backspace) will terminate the test at any time.

VOLT FREQ MAX

This test will set the voltage and frequency for a level defined by Table 9-8. The test will last for
30 minutes. The test will be repeated using the voltage from Table 9-7 and frequency from
Table 9-8. The

key (backspace) will terminate the test at any time.

VOLT UNBALANCE

Standard/Group

RTCA

Group1

Group2

Group3

Voltage offset

8

8

8

12

Frequency

400

400

360/650

360/800

Table 9-9: Emergency Voltage Unbalance

This test will change the output voltage for each phase from 115 volts to 115V + offset. Refer to
Table 9-9 for the offset value and the Frequency. The test will last 30 minutes. The test will be
repeated for a second Frequency if applicable. The

key (backspace) will terminate the test at

any time.