connected to a stable Earth ground. Alternatively, two each of two-electrode configurations

can be used (contact manufacturer for details). Table 25 provides a list of three-electrode

Gas Discharge device manufacturers.

Table 25. Manufactures of Suggested Gas Discharge Arresters

Vendor and Configuration

Series

Voltage

Sankosha, 3 Electrode

www.sankosha-usa.com/arresters.asp?id=2

3H or 3P

90 VDC

Citel, 3 Electrode

www.citelprotection.com/citel/gas_cover.htm

BT, BTR, or BTS

90 VDC

Littelfuse, 3 Electrode

www.littelfuse.com/series/PMT8.html

PMT8

90 VDC

Figure 35 shows a typical outdoor twisted pair network in which Gas Discharge arresters

have been incorporated.

Figure 35. Network and Shield Lightning Protection

When the network data line extends outside of a building or grounded structure, every FT

6000 Smart Transceiver or Neuron 6000 Processor device on the network segment, whether

located indoors or outdoors, must be equipped with surge protection circuitry. Additionally,

protection devices must be added to the network at every point where the network cable exits

the building or structure.