Echelon Series 6000 Chip databook User Manual
Page 99
connected to a stable Earth ground. Alternatively, two each of two-electrode configurations
can be used (contact manufacturer for details). Table 25 provides a list of three-electrode
Gas Discharge device manufacturers.
Table 25. Manufactures of Suggested Gas Discharge Arresters
Vendor and Configuration
Series
Voltage
Sankosha, 3 Electrode
3H or 3P
90 VDC
Citel, 3 Electrode
BT, BTR, or BTS
90 VDC
Littelfuse, 3 Electrode
PMT8
90 VDC
Figure 35 shows a typical outdoor twisted pair network in which Gas Discharge arresters
have been incorporated.
Figure 35. Network and Shield Lightning Protection
When the network data line extends outside of a building or grounded structure, every FT
6000 Smart Transceiver or Neuron 6000 Processor device on the network segment, whether
located indoors or outdoors, must be equipped with surge protection circuitry. Additionally,
protection devices must be added to the network at every point where the network cable exits
the building or structure.
Series 6000 Chip Data Book
87