beautypg.com

Network connection, Network topology overview – Echelon Series 6000 Chip databook User Manual

Page 104

background image

Network Connection

For a TP/FT-10 channel, the network connection (from the NETP and NETN pins) is polarity

insensitive. Therefore, either of the two twisted pair wires can be connected to either of

these network connections.
For any of the supported cable types, the average temperature of the wire must not exceed

+55 °C, although individual segments of wire can be as hot as +85 °C.
As a general rule, TP/FT-10 network channel communication cables should be separated

from high voltage power cables. Follow local electrical codes with regard to cable placement.

Network Topology Overview

The TP/FT-10 network is designed to support free topology wiring, and can accommodate

bus, star, loop, or any combination of these topologies. Series 6000 devices can be located at

any point along the network wiring. This capability simplifies system installation, and

makes it easy to add devices if the network needs to be expanded. Figure 36 through Figure

40 present five different network topologies. The actual termination circuit varies by

application.

Figure 36. Singly Terminated Bus Topology

Figure 37. Doubly Terminated Bus Topology

92

Network Cabling and Connections for FT Devices