procedures for TP/FT-10 channels, be sure to include the TP/FT-10 system specifications and,

based upon the cable used, the appropriate transmission distance specifications.

Incorporating these specifications can ensure a smoother installation, and provide a resource

for the installer who must troubleshoot the installation.
Note: The following specifications apply to a single network segment. You can combine

multiple segments by using FTT-10A based physical layer repeaters to increase the number

of devices and distance as described in the FTT-10A Free Topology Transceiver User’s Guide.

System Specifications

Each network segment can include up to 64 FT-X3 (or FT X1 or FT-X2) Transformers and FT

Smart Transceivers.
You can use LPT-11 transceivers on network segments with FTT-10A transceivers and FT

Smart Transceivers, but they are subject to additional constraints, particularly on distance.

See the LONWORKS LPT-11 Link Power Transceiver User's Guide for more information.
The average temperature of the wire must not exceed +55°C, although individual segments

of wire may be as hot as +85°C.
As a general rule, the TP/FT-10 channel communication cables should be separated from

high voltage power cables. Follow local electrical codes with regard to cable placement.

Transmission Distance Specifications

Table 27 and Table 28 list the transmission distance specifications for the supported cable

types.

Table 27. Doubly Terminated Bus Topology Specifications

Cable Type

Maximum Bus Length (Meters)

Belden 85102

2700

Belden 8471

2700

NEMA Type 4, 22 AWG

1400

J-Y(ST)Y 2x2x0.8

900

ANSI/TIA/EIA Category 5 or 6

900

A doubly-terminated bus can have stubs of up to 3 meters from the bus to each device.

Table 28. Free Topology Specifications

Cable Type

Maximum Device-to-

Device Distance (Meters)

Maximum Total Wire

Length (Meters)

Belden 85102

500

500

Belden 8471

400

500

NEMA Type 4, 22 AWG

400

500

Series 6000 Chip Data Book

95