beautypg.com

Cyclic communication] with handshake, Message communication] with handshake, For the control logix/compact logix (rslogix 5000) – KEYENCE SR-750 Series User Manual

Page 106: For the kv series, For the micro logix (rslogix 500)

background image

106

E SR-750 UM

„

For the Control Logix/Compact Logix (RSLogix 5000)

Description of tags used in the sample

Reference program chart

Description of the reference program

Rung1 : This starts Read Request and starts reading.
Rung2 : With the rising of Result Complete, the data written to Result Data are

copied to READ_DATA.

Rung3 : When Read Complete is ON, Read Complete Clear turns ON.

[Cyclic communication] with handshake

This is a reference program to start/stop reading or load data by using the cyclic
communication with handshake.

„

For the KV Series

Reference program chart

Description of the reference program

Row 1 : When the timing (REQ) signal turns ON, Read Request turns ON.
Row 2 : When Read Data Reception Available turns ON and Read Data

Reception Complete turns OFF, Read Data Update Permitted turns ON.
Read Data Update Permitted is self-retained.
* Read Data Reception Available turns ON when read data is buffered

to SR-750.

Row 3 : When Read Data Reception Complete turns ON, the data for the

specified bytes are transferred from read data to DM1000.
* Read Data Reception Complete turns ON when writing read data from

SR-750 to PLC is complete.

Row 4 : When Read Complete is ON, Read Complete Clear turns ON.

Name

Data type

Description

REQ

BOOL

Bit to order to start/stop reading

READ_DATA

SINT[256]

Memory to store read data

( )

( )

ONS

Rung1

Rung2

Rung3

REQ

Source (I)Result

Data[0]

Dest READ_DATA[0]

Length (I)Result Data Size

(O) Read Request

(O) Read Complete Clear

(I) Read Complete

(O) : Output Assemblies
(I) : Input Assemblies

(O) Read Complete

BMOV

WOE

DM1000

#100

REQ

Row 1

Row 2

Row 3

Row 4

(I) Read Data Reception Available

(I) Read Data Reception Available

(O) Read Data Update Permitted

(I) Read Request

(O) Read Complete Clear

(O) : Output Assemblies
(I) : Input Assemblies

(O) Read Data Update Permitted

(I) Read data Reception Complete

(I) Read Complete

„

For the Control Logix/Compact Logix (RSLogix 5000)

Description of tags used in the sample

Reference program chart

Description of the reference program

Rung1 : When the timing (REQ) signal turns ON, Read Start Request turns ON.
Rung2 : When Read Data Reception Available turns ON and Read Data

Reception Complete turns OFF, Read Data Update Permitted turns ON.
Read Data Update Permitted is self-retained.
* Read Data Reception Available turns ON when read data is buffered

to SR-750.

Rung3 : When Read Data Reception Complete turns ON, read data is

transferred to READ_DATA.
* Read Data Reception Complete turns ON when writing read data from

SR-750 to PLC is complete.

Rung4 : When Read Complete is ON, Read Complete Clear turns ON.

[Message communication] with handshake

This is a reference program to start/stop reading or load data in message
communication.

„

For the Micro Logix (RSLogix 500)

Description of tags used in the sample

Name

Data type

Description

REQ

BOOL

Bit to order to start/stop reading

READ_DATA

SINT[256]

Memory to store read data

Name

Data type

Description

B9:0/0

Binary

Bit to order to start/stop reading

T10

Timer

Timer

N11

Integer

Memory that stores Bank No.

MG20

Message

Message to perform Read Complete Clear

MG21

Message to perform Read Start

MG22

Message to perform Get Attribute Single for Read
Status

MG23

Message to perform Get Result Data

MG24

Message to perform Read Stop

N25

Integer

Memory that stores Get Attribute Single result of
MG22

N26

Integer

Message command to receive the result data

N27

Integer

Memory that stores Get Result Data result of MG23

RIX30

Extended
Routing
Information

Extended Routing Information for MG20

RIX31

Extended Routing Information for MG21

RIX32

Extended Routing Information for MG22

RIX33

Extended Routing Information for MG23

RIX34

Extended Routing Information for MG24

( )

( )

( )

/

REQ

Rung1

Rung2

Rung3

Rung4

ONS

Source (I) Read Data [0]

Dest READ_DATA[0]

Length (I) Read Data Size

(I) Read Data Reception Available (I) Read data Reception Complete

(O) Read Request

(O) Read Data Update Permitted

(O) Read Complete Clear

(O) : Output Assemblies
(I) : Input Assemblies

(O) Read Data Update Permitted

(I) Read data Reception Complete

(I) Read Complete