To test the 0-10v output mode:

1. Enter the Setup Mode (see Setup Mode on page 40).
Chngs

Poss!

P110.-- ~ F.S.= ~ 100.00

2. Attach the voltmeter + (red) lead to pin 3 (0-10VDC) and the - (black) lead to pin 2 (ISOLATED GND)

of the Analog Output connector.

3. Key

in

!

.

Test ~ 0-10v

Per

P176

4. Press

1

or

(

to set the output to 0%.

0-10v

~

0P

0.00

VDC

5. Press

1

or

(

to increase the output to 25%.

0-10v

~

25P

2.50

VDC

6. Press

1

or

(

to increase the output to 50%.

0-10v

~

50P

5.00

VDC

7. Press

1

or

(

to increase the output to 75%.

0-10v

~

75P

7.50

VDC

8. Press

1

or

(

to increase the output to 100%.

0-10v

~

100P

1.00 VDC

To test the 0-20mA output mode:

Voltmeter readings are based on the use of a 500 ohm precision resistor. Caution! Do not exceed
500 ohms.

1. Enter the Setup Mode (see Setup Mode on page 40).
Chngs

Poss!

P110.-- ~ F.S.= ~ 100.00

2. Attach the precision resistor to pin 5 and pin 6.

3. Attach the voltmeter + (red) lead to pin 6 (0-20 mA) of the analog output connector.

4. Attach the voltmeter - (black) lead to pin 5 (ISOLATED GND) of the Analog Output connector.

5. Key

in

!

(see Setup Mode on page 40).

Test ~ 0-20A

Per

P176