Holtgreven GSE-355 I.S. User Manual
Page 30
21
To test the 0-10v output mode:
1. Enter the Setup Mode (see Setup Mode on page 40).
Chngs
Poss!
P110.-- ~ F.S.= ~ 100.00
2. Attach the voltmeter + (red) lead to pin 3 (0-10VDC) and the - (black) lead to pin 2 (ISOLATED GND)
of the Analog Output connector.
3. Key
in
!
.
Test ~ 0-10v
Per
P176
4. Press
1
or
(
to set the output to 0%.
0-10v
~
0P
0.00
VDC
5. Press
1
or
(
to increase the output to 25%.
0-10v
~
25P
2.50
VDC
6. Press
1
or
(
to increase the output to 50%.
0-10v
~
50P
5.00
VDC
7. Press
1
or
(
to increase the output to 75%.
0-10v
~
75P
7.50
VDC
8. Press
1
or
(
to increase the output to 100%.
0-10v
~
100P
1.00 VDC
To test the 0-20mA output mode:
Voltmeter readings are based on the use of a 500 ohm precision resistor. Caution! Do not exceed
500 ohms.
1. Enter the Setup Mode (see Setup Mode on page 40).
Chngs
Poss!
P110.-- ~ F.S.= ~ 100.00
2. Attach the precision resistor to pin 5 and pin 6.
3. Attach the voltmeter + (red) lead to pin 6 (0-20 mA) of the analog output connector.
4. Attach the voltmeter - (black) lead to pin 5 (ISOLATED GND) of the Analog Output connector.
5. Key
in
!
(see Setup Mode on page 40).
Test ~ 0-20A
Per
P176