Setting up station on servera, Setting up station on servera -67 – Rockwell Automation 1757-SWKIT3200 ProcessLogix R320.0 Installation and Upgrade Guide User Manual
Page 87
Publication 1757-IN032B-EN-P - April 2001
System Software Upgrade Procedures 1-67
19. If you have redundant LANs, you must repeat Step 3 through
Step 18 to set up files for the second LAN using the name or IP
address of the SERVERA and SERVERB nodes specified in the
Hosts file for the second LAN.
20. Click Station
⇒
Exit.
21. Click OK to exit Station.
Setting Up Station on SERVERA
Use the following procedure to connect a ProcessLogix Client Station to
the Primary Server (SERVERA).
1. On the SERVERA node, click Start
⇒
Programs
⇒
ProcessLogix
Server
⇒
Station.
2. Click Cancel at the Unable to connect prompt, if applicable.
3. Click Station
⇒
Setup to call up the Station Setup dialog box.
4. Click the down arrow in the Server Connection field and select
Network (TCP/IP).
5. Click Setup
in the Server Connection field to call up the
TCP/IP Setup dialog box. Make these entries:
a. Key in the name or IP address of the SERVERB (PLX1B) node
specified in the Hosts file in the Server Name field.
This function sets up the correct file reference for SERVERB on
the SERVERA node.
b. Select the Static option.
c. Key in >1< as the Station number.
EXAMPLE
For example, the Secondary Server (SERVERB) name
would be PLX1B1 based on a Server name of PLX1B
in Step 5 and the Primary (SERVERA) name would
be PLX1A1 based on a Server name of PLX1A in
Step 13.
Refer to the Server/Client Configuration Guide in
Knowledge Builder for more information.
The Server names used are for example purposes only
and must not be used in place of your actual Server
names.