6-18 New Functions and Features
In the Channel Name field select the channel defined earlier. In the
Definition field type the following:
2 NAME=name ID=id1 STN=id2 MONITOR_ADDR=addr
where:
name
is the name of the controller with a maximum of 10
characters
id1
is the ControlNet MAC address of the first PLC in the
redundant PLC pair
id2
is the ControlNet MAC address of the second PLC in the
redundant PLC pair
addr
is the file and word address in the PLC where backup
status of the PLC is stored, for example: N12:3. Must not
exceed 6 characters.
Using Quick Builder to Configure Points
Quick Builder is used to define and configure points to reference data
in an Allen-Bradley PLC. Points belonging to a redundant
Allen-Bradley controller are defined in the same way as those defined
for other types of connection for Allen-Bradley. For details on defining
and configuring points refer to the Quick Builder online help.
Improved Industrial Shape Files
New versions of some commonly used industrial shapes have been
included in the Pipes area of the Industrial shape gallery in this
release. These new shape files have a reduced memory footprint. The
new shape files are:
•
Pipebend1.dsp
•
Pipebend2.dsp
•
Pipebend3.dsp
•
Pipebend4.dsp
•
Pipeflange1.dsp
•
Pipeflange2.dsp
•
Pipeflange3.dsp
•
Pipeflange4.dsp