7-14 Performance and Capacity Specifications
I/O Specifications
Table 7.Q I/O Module Capacity
I/O Module and Fieldbus Capacity
50 ms CEE
5 ms CEE
Maximum Number of IOMs per 1757-PLX52
(1756/1757 + 1797 FLEX EX + 1794-FLEX I/O + CN2FFs in any
combination, exceptions noted below.)
64
12
(local 1757/1756
I/O only)
Maximum Number of Analog IOMs per 1757-PLX52
(including Pulse Input Modules)
64
12
(local 1757/1756
I/O only)
Maximum Number of Serial Interface Modules per
1757-PLX52
3
1
Maximum Number of FTA assemblies per Serial Interface
Module
•
Each FTA connected counts as 4 IOMs in the 64 Max
IOM calculation above and the 24 IOMs/1756-CNB
calculation below.
2
2
Maximum Number of Remote I/O Chassis +
1794/1797-ACNR15s (combined) per 1757-PLX52.
8
0
(local 1757/1756
I/O only)
Maximum Number of IOMs per Downlink 1756-CNB -
1756/1757 + 1797 FLEX Ex and 1794 FLEX I/O + CN2FFs in
any combination (with TC-MUX021, 1757-PIM and CN2FF
limitations as noted elsewhere)
•
Each Pulse Input Module counts as 1.5 IOMs in the
24 IOM/1756-CNB calculation (but not the 64
IOM/1757-PLX52 limit).
64 scheduled
24
unscheduled
0
(local 1757/1756
I/O only)
Maximum number of Downlink 1756-CNB’s per Controller
Chassis
4
0
Maximum number CN2FFs per 1757-PLX52
•
Each Linking Device counts as 1 IOM in the 64
IOM/1757-PLX52 calculation above.
8
0
(local 1757/1756
I/O only)
Maximum number CN2FFs per Non-Redundant Server
8
0
(local 1757/1756
I/O only)
Maximum number CN2FFs per Redundant Server (NI-FBUS
Service and NI Configurator must be run on the Backup
Server only)
16
0
(local 1757/1756
I/O only)
Maximum number CN2FFs per NI Configurator Project
1
0
(local 1757/1756
I/O only)
Maximum Number of H1 segments per CN2FF
2
N/A
Maximum number of CN2FF Devices per H1 segment
connected to a CN2FF.
10
N/A