Publication 1757-IN032B-EN-P - April 2001
5-24 Supplementary Procedures
2. Close any open Control Module and/or Sequential Control
Module.
For a system with redundant ProcessLogix Servers, be certain that
the databases are synchronized and you are using the SERVERB
node. Refer to Synchronizing ERDB on Redundant Servers on
page 1-63.
3. In Monitoring tab, click the plus sign in the tree root path to the
non-redundant 1757-PLX52 being made redundant to display the
CEE folder icon.
4. Click the CEE folder icon.
5. Click Tools
⇒
Upload with Contents to upload the existing
controller database.
6. Click Continue.
This may take considerable time to complete, depending on the
amount of CM/SCMs [and their number of FBs and/or number of
Steps/Transitions] currently assigned to this CEE.
7. Click the CEE folder icon.
8. Click Tools
⇒
Update with Contents (to Project) to save the
existing controller database. Click Continue.
This may take considerable time to complete, depending on the
amount of CM/SCMs [and their number of FBs and/or number of
Steps/Transitions] currently assigned to this CEE.
9. Click the CEE folder icon to select it.
10. Click Operate
⇒
Inactivate
⇒
This CEE’s SCMs to inactivate all
assigned SCMs, if applicable.
11. Click Yes in the dialog box to confirm the action.
12. Click Operate
⇒
Inactivate
⇒
This CEE and its IOMs and CMs to
inactivate the CEE and all assigned IOMs and CMs.
13. Click Yes in the dialog box to confirm the action.
Color of all icons changes to Blue.
14. Select the contents (CMs, SCMs, IOMs) of the CEE folder and click
Edit
⇒
Delete.