3-32 Full PC Software Installation Procedures

6. In the graphic pane, select the Supervisory Uplink CNB and click

Change ControlNet Parameters

.

7. Change UMax to 24 and click OK.

8. Click Yes to confirm the action.

9. Click OK.

10. Close NTOOLS.

Updating the 1784-PCIC Network Address

1. Click Start

Programs

Rockwell Software

RSLinx

RSLinx

to call up the Rockwell Software RSLinx window.

2. Click Communications

Configure Drivers to call up the

Configure Drivers dialog box.

3. Select AB_PCIC-1 in the Configured Drivers list box and click

Configure.

4. In the Configure 1784-PCIC window, enter 24 for the new

Network Address for the PCIC and click OK.

5. Restart the PC.

ATTENTION

!

Before continuing, you MUST exit all ProcessLogix
applications and stop all ProcessLogix services.

Refer to Stopping ProcessLogix Applications and
Services on page 1-8.