Upgrade r400.0 sp2 server to r510.0, Upgrade r400.0 sp2 server to r510.0 -3 – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual
Page 87

Publication 1757-IN510A-EN-P - October 2003
ProcessLogix Server Upgrade Procedures 4-3
Upgrade R400.0 SP2 Server to R510.0
This section describes the steps necessary to upgrade the
ProcessLogix R400.0 SP2 Server software to R510.0. There are two
upgrade options.
Option 1: Upgrading R400.0 SP2 Server to R510.0 - Clean Install
a. Backup your data.
b. Complete a clean install.
c. Restore your data.
The following table lists the items in Option 1 that you
MUST
complete to upgrade an R400.0 SP2 Server to an R510.0 Server.
IMPORTANT
Due to the nature of this upgrade, it is strongly
recommended that you follow Option 1 when
upgrading from R400.0 SP2 to R510.0.
TIP
Upon restarting the system, you may receive a
message that a service failed to start. If you receive
this message, click
OK.
Table 4.C Option 1: Upgrading R400.0 SP2 Server to R510.0 Checklist
✔
Step
Item
Page
1 .
Preparing for a ProcessLogix R400.0 SP2 or R500.1 to R510.0
Server Upgrade
2.
Saving R400.0 SP2 or R500.1 Data to a Remote PC
3.
Clean System Windows 2000 Server Installation
4.
Windows 2000 Service Pack 4 Installation
5.
Windows Security Hotfix Installation
6.
Internet Explorer 6.0 SP1 Installation
7.
8.
9.
Additional Operating System Customization Procedures
1 0.
Creating Emergency Repair Disks
1 1 .
Copying R400.0 SP2 or R500.1 Data to the R510.0 Server
1 2.