Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual
Page 121

Publication 1757-IN510A-EN-P - October 2003
ProcessLogix Server Upgrade Procedures 4-37
8. Enter the New Password, Confirm the New Password and click
OK.
The message
Passwor d accepted should appear in the message
zone. If it does not, repeat steps 7 and 8.
If migrating a system with Fieldbus devices, continue with Adding
Saved Device Templates Using Fieldbus Library Manager on page
4-37. Otherwise skip to Importing the Database Using Control Builder
on page 4-38.
Adding Saved Device Templates Using Fieldbus Library Manager
For a redundant Server pair, complete these steps on
SERVERB only.
1 . Click Star t
⇒ Pr ograms ⇒ Pr ocessLogix Engineering Tools
⇒ Fieldbus Library Manager.
2. In the Login dialog box, make these entries:
a. Enter >mngr< as the default User Name.
b. Enter the appropriate password.
c. Select
Classic Ser ver Secur ity in the Domain Name
drop-down list.
3. Click File
⇒ Open Device.
4. Browse to your FFDevices backup directory, select a device and
click
OK.
For example: C:\UpgradeData\FFDevices
5. Click File
⇒ Save.
6. If necessary, click Yes at the Resolve Load Destination window.
7. Click OK.
8. Click File
⇒ Build Device Template ⇒ Fr om Curr ent
Device.
Do not use the From Existing .DEF files option.
9. Click OK to confirm file addition.
1 0. Repeat Steps 3-9 for each device stored in the FFDevices backup
directory.
1 1 . Close the Fieldbus Library Manager.