8 - supplementary procedures, Stopping processlogix applications and services, Chapter 8 – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual
Page 203: Supplementary procedures, Stopping processlogix applications and services -1, Chapter

1
Publication 1757-IN510A-EN-P - October 2003
Chapter
8
Supplementary Procedures
Stopping ProcessLogix
Applications and Services
This section describes how to stop ProcessLogix services in the
Windows 2000 system. Use the following procedure to exit all
ProcessLogix applications and stop all ProcessLogix services.
1 . Exit all running ProcessLogix applications, such as Control
Builder, Station, and Network Tools (NTOOLS).
2. Right-click the My Computer icon and select Manage.
3. Expand Ser vices and Applications.
4. Select Ser vices.
5. Stop these Services in the following order:
a. ProcessLogix Server Daemon (also stops ProcessLogix Server
Operator Management and ProcessLogix Server System, if
applicable)
b. ProcessLogix Server Database
c. ProcessLogix Server Desktop
d. ProcessLogix Server Logger
e. Windows Management Instrumentation
f. ProcessLogix Control Data Access Server
g. ProcessLogix System Repository
h. ProcessLogix ER Server
i. RSLinx
j. XLNet Daemon
ATTENTION
!
Before installing or uninstalling any software
component, you
MUST exit all ProcessLogix
applications and stop all ProcessLogix services.
If you have a redundant Server pair, you must
complete this procedure on
SERVERB first. Then
complete the entire procedure again on
SERVERA.
TIP
To stop a ser vice:
If the service is present, right-click it and select
Stop.
If prompted, click
Yes to also stop other services. If a
service is already stopped, move on to the next one
in the list below.