Additional Redundant Server Procedures 6-17
1 2. Click Cancel at the Unable to connect prompt, if applicable.
1 3. Click Station
⇒ Connect to call up the Station Connect dialog
box.
1 4. Select Default and click Edit Connection.
1 5. On the Connection tab, make these entries to have the Station
point to
SERVERA (PLX1 A):
a. In the Server field, enter or
Br ow se to the Primary Server
name,
SERVERA.
b. Select the Station type as
Static Station.
c. Enter >2< as the Static Station Number and click Advanced.
d. Check the
Aux iliar y setup file checkbox.
e. Click
Br owse and navigate to:
C:\Honeywell\Client\Station\defaultb.stn and click
Open.
1 6. Click Save.
1 7. Click Yes to save changes.
1 8. Select Default and click Connect.
1 9. Click Cancel at the Unable to connect prompt, if applicable.
20. If you have redundant LANs, you must repeat Step 1 through
Step 19 to set up files for the second LAN using the name or IP
address of
SERVERA and SERVERB specified in the Hosts file
for the second LAN
.
Navigate in Knowledge Builder to Server and Client
Configuration Guide
⇒
Configuring and Monitoring a
Redundant Server System
⇒
Configuring Stations for Server
Redundancy
⇒
Dual Network Configuration for more
information.
21 . Click Station
⇒ Exit.
22. Click Yes to exit Station.
IMPORTANT
You must indicate the full path to the .stn file.