Adding redundancy to r510.0 non-redundant, Server systems -2 – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual
Page 162

Publication 1757-IN510A-EN-P - October 2003
6-2 Additional Redundant Server Procedures
Adding Redundancy to
R510.0 Non-Redundant
Server Systems
If your Servers are already named A and B (
SERVERA and SERVERB),
skip to Completing the ProcessLogix R510.0 Setup on a Redundant
Server Pair on page 6-2.
If you are adding Server redundancy to a non-redundant system,
designate an existing R510.0 non-redundant Server as
SERVERA
(Primary). Designate the other Server as
SERVERB (Secondary).
Perform the following procedures on Primary (
SERVERA) and
Secondary (
SERVERB) Servers.
Changing the Computer Name on a ProcessLogix Server
Refer to Changing the Computer Name on a ProcessLogix Server on
page 8-16.
Completing the
ProcessLogix R510.0 Setup
on a Redundant Server Pair
Use the following procedures to configure a redundant server pair
after ProcessLogix R510.0 software has been installed. If you need to
install ProcessLogix R510.0 software, refer to Table 1.B on page 1-3.
ATTENTION
!
Be certain that your process is off control before you
begin any upgrade procedure. This means the
1757-PLX52 should be in the Idle state.
ATTENTION
!
Be certain that your process is off control before you
begin any upgrade procedure. This means the
1757-PLX52 should be in the Idle state.