Publication 1757-IN510A-EN-P - October 2003
Firmware Maintenance Procedures 7-5
Interface module (TC-MUX021) to match the current ProcessLogix
software version before you can download a control strategy.
Firmware Revision Level
Reference
The following table lists the firmware revision levels for listed
components that are current for R510.0 along with the directory
locations for firmware upgrade files.
IMPORTANT
Firmware versions for these modules are not
qualified for backward compatibility. For example, if
you try to use a 1757-PLX52 with a firmware version
that is compatible with R510.0 with a Server running
software version R300.1, the control and operation of
the system is not guaranteed.
ATTENTION
!
This release of ProcessLogix supports only the
firmware versions listed in Table 7.A. When installing
new systems or repairing existing systems, you must
ensure that all modules meet the firmware version
requirements listed in Table 7.A.
Be certain that your process is off control before you
begin any upgrade procedure. This means the
1757-PLX52 should be in the Idle state.
Table 7.A Hardware component firmware revision level reference for R510.0
Component Name
Model Number
Revision Level
for R510.0
Directory
File
Process Controller
Module
1757-PLX52
(redundant-
compliant)
AV 500.1-01.1
BV 500.1-01.1
C:\Honeywell\tps50\system\bin
Cee5.pcm
Cee50.pcm
Cpmboot.pcm
Serial Interface
Module (SIM)
TC-MUX021
AV 500.1-01.1
BV 500.1-01.1
C:\Honeywell\tps50\system\bin
Simboot.pcm
simrex.pcm
Use this base directory path to locate the firmware directories and files for the following modules:
C:\Honeywell\tps50\system\firmware
Redundancy
Module (RM)
1757-SRM
AV 3.29
BV 3.2
\1757-SRM\3_29
99450209.nvs