Upgrading hardware component firmware, Upgrading hardware component firmware -40 – Rockwell Automation 1757-SWKIT5100 ProcessLogix R510.0 Installation and Upgrade Guide User Manual
Page 124

Publication 1757-IN510A-EN-P - October 2003
4-40 ProcessLogix Server Upgrade Procedures
1 1 . To import the data, enter >sysbld -restore C:\
Honeywell\server\backup\data -y< and press
Depending on the size of your database, this step may take
several minutes.
1 2. To start the ProcessLogix Server enter >hscserver /start /y< and
press
1 3. Close the command prompt.
Upgrading Hardware Component Firmware
1 . Refer to 1784-PCIC Driver Installation on page 7-1 and
1784-PCIC Firmware Installation on page 7-3 to upgrade the
1784-PCIC to the supported driver and firmware revisions.
2. Refer to Loading 1757-PLX52, TC-MUX021, or 1757-FIM Boot
and Personality Images on page 7-9 to
upgr ade the 1757-PLX52
boot and personality images to the current release level.
3. After upgrading the 1757-PLX52, refer to Upgrading Hardware
Component Firmware on page 7-4 to check if other hardware
components require upgrades.
IMPORTANT
Stop! It is mandatory that you check the firmware
revision levels for
ALL ProcessLogix hardware
components after a ProcessLogix software
installation and/or a component addition or
replacement.
Do
not proceed until you have upgr aded the
firmware. Then go to the next section, Backing Up a
ProcessLogix Server Hard Drive to Tape.
ATTENTION
!
If you also upgraded from a non-redundant
1757-PLX52 to a redundant 1757-PLX52, you must
delete the existing CPM and its associated CEE from
the Project tab, reconfigure a new 1757-PLX52 and its
associated CEE, and reassign the components before
you download the CPM to the Controller.